Every conventional rapid filter pays for its control precision with hardware: influent valves, wash-water valves, filtered-water valves, drain valves, plus the actuators to drive them. The siphon filter takes a different bargain. It gives up the valves entirely and lets two hydraulically primed siphons — one on the influent side, one on the wash-water discharge — do the switching instead. Because water level alone starts and stops the washing cycle, the whole unit becomes far easier to automate, which explains why it has found fairly wide application across municipal and industrial water plants.

Siphons Instead of Valves

The defining arrangement is simple to state but has deep consequences. Influent water reaches each cell through an influent siphon, and spent wash water leaves through a wash-water siphon, so the large gate valves of a conventional rapid filter disappear. What remains is a low-head-loss distribution system under the media, a clear-water channel that stores the filtered output, and a vacuum control system mounted above the central pipe gallery. The filter body is built as one integral concrete structure of 6–8 cells, mostly rectangular, although circular layouts are workable for small flows.

During filtration the filtered-water level always stands higher than the top of the media bed. The bed therefore works under positive head at all times, and the negative-head zones that complicate the operation of ordinary rapid filters never develop. Each cell sits at a slightly different water level, and that difference simply mirrors the head loss accumulated across its own media layer.

The Backwash Sequence, Step by Step

Washing starts with the influent, not the wash water. The vacuum in the influent siphon is broken first, so the distribution channel stops feeding the cell while filtration within it continues. The cell water level drops quickly at first, then levels off — that plateau is the cue to begin washing. The vacuum system then extracts air from the wash-water siphon, priming a siphon that draws the standing water down to the lower part of the filter center and out through the wash drainage pipe. Once enough level difference has built up between the clear-water channel and the cell, the backwash proper begins, and the wash water follows essentially the same path as in a conventional rapid filter. When the media runs clean, breaking the vacuum in the wash siphon stops the flow immediately; the influent siphon is restarted, and the cell returns to filtration.

How Many Cells the Wash Flow Demands

Because the wash water comes from the filter's own output, the other cells must keep producing while one cell is washed. Two relations govern the balance. The backwash intensity follows q = nQ/F, where q is the wash intensity in L/(s·m²), Q the filtration flow of one cell, F the area of one cell and n the number of cells under filtration. The cell count must also satisfy n ≥ 3.6q/v, with v the filtration rate in m/h. Plugging in a backwash intensity of 10–15 L/(s·m²) and a filtration rate of 8 m/h shows why at least 5–7 cells are required. Raising the filtration rate trims the cell count, but it also loads each bed faster — a trade every designer weighs against the media and the wash schedule.

Depth Budget and the Low-Head-Loss Constraint

A siphon filter stands deeper than the machine it replaces, because the wash-water head has to be stored inside the structure itself. Designs built in China typically run 4.5–5 m deep, assembled from eight components. H8 is freeboard of 0.1–0.3 m. H1 is the underdrain plenum at the bottom, generally 0.3 m. H2 is the height of the low-head-loss distribution system. H3 is the media thickness, set by design requirements. H4 is the bed expansion during backwash, taken as H3·e%. H5 is the total height of the wash-water troughs, counting clear trough height plus structural bottom thickness of about 0.1 m. H6 is the level difference between the effluent control weir and the trough rim — the available wash-water head, only 1.0–1.3 m. H7 is the maximum filtration head of 1.5–2.0 m. Total filter depth is the sum of all eight.

That available wash head of roughly 1.1–1.3 m is the binding constraint of the whole design. It rules out any high-loss underdrain, so the distribution system must be one of the low-head-loss types: double-layer perforated plates, plate-and-mesh systems, triangular-channel perforated plates, perforated filter bricks or slit-type nozzles. Small filters favor nozzles, large filters favor double-layer perforated plates. Slit-type nozzle systems have proven reliable in siphon filters, valveless filters, pressure filters and ion exchangers alike, and they allow the gravel support layer to be omitted, reducing filter depth. The price is more complex installation and higher cost: about 40–60 nozzles are installed per square meter, each with a slit area of 100–350 mm², totalling roughly 0.5–2% of the filter area. On steel or cast-iron plates the nozzles screw directly into tapped holes without a base; on reinforced-concrete plates they attach to a short pipe embedded in a base.

The Vacuum Plant Behind It All

None of this works without the vacuum siphon system, an essential part consisting of a vacuum pump, a vacuum tank, piping with control valves, and the influent and wash siphons themselves. Water ejectors can replace the vacuum pump. The vacuum tank is optional: it stays where centralized control is wanted, and is omitted where the ejector or pump can prime the siphons directly. The siphons are sized for the flow they must pass, with circular or rectangular cross-sections, welded from steel plate or made of cast-iron pipe. The pump is selected to extract the required air volume within the planned priming time, with an appropriate margin; priming the wash siphon should take about 2–5 minutes.

What It Wins, What It Costs

Against a conventional rapid filter of the same capacity, the gains are concrete. No large gate valves or their electric and hydraulic actuators are needed. Washing uses the filter's own effluent flow and head, with no wash-water tower or pump. Within a certain range, filtration rates across the cells rebalance automatically and evenly as inflow varies, with no rate-control devices. The filtered-water level stays above the media, so positive head is preserved and negative head cannot occur. Control valves and piping concentrate around the central vacuum tank, making the pipe gallery small, operation convenient, automation easy, staffing lighter and running costs lower. Investment typically lands 20–30% below a conventional rapid filter, with 30–40% savings in metal materials.

The drawbacks are equally specific. The structure is deep — 5–6 m in practice. The low-head-loss distribution system caps the cell area, because the wash-water head is limited by filter depth and offers at most about 1.3 m with no surplus to adjust, so backwashing is sometimes less effective than operators would like. Plants that need aggressive washing of heavily loaded beds have to weigh these limits against the civil savings before choosing the siphon configuration.